--	HWg-PWR MIB 1.02
--		History:
--
--		1.00	 2.04.2010 Marek Hummel  - Created
--		1.01	 2.04.2010 Marek Hummel  - Add Input Dry Contacts
--		1.02	 20.2.2017 Marek Hummel  - Fix pwrStateToAlarm, pwrStateToNormal trap definition, rename mtvalValue to mtvalMbusValue								
-- 		1.03	 9.10.201  Marek Hummel  - Add meter secondary address in text format 
--

HWG-PWR-MIB DEFINITIONS ::= BEGIN
IMPORTS
	OBJECT-TYPE			FROM RFC-1212
	TRAP-TYPE			FROM RFC-1215
	enterprises			FROM RFC1155-SMI
	sysName, DisplayString		FROM RFC1213-MIB
	TRAP-TYPE			FROM RFC-1215;

--
-- Type Definitions
--
PositiveInteger ::= INTEGER (1..2147483647)	-- 0x7FFF FFFF
Txt8 ::= DisplayString (SIZE (0..8))
Txt16 ::= DisplayString (SIZE (0..16))
SensorValue ::= INTEGER
SensorID ::= INTEGER

OpenClose ::= INTEGER {
		open (0),
		close (1)
	}

AlarmState ::= INTEGER {
		invalid (0),
		normal (1),
		alarm (2)
	}

--
-- Node Definitions
--

hwgroup		OBJECT IDENTIFIER ::= { enterprises 21796 }
x390		OBJECT IDENTIFIER ::= { hwgroup 4 }
hwgpwr		OBJECT IDENTIFIER ::= { x390 6 }

-- Root objects
info		OBJECT IDENTIFIER ::= { hwgpwr 70 }
meters		OBJECT IDENTIFIER ::= { hwgpwr 1 }
input		OBJECT IDENTIFIER ::= { hwgpwr 2 }

infoAddressMAC OBJECT-TYPE
	SYNTAX	DisplayString (SIZE (0..17))
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"MAC address in text form.
		It is here to distinguish devices in trap messages."
	::= { info 1 }

-- Meters Number -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 
mtNumber OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Pocet pripojenych M-BUS meridel"
	::= { meters 1 }

-- Meter Table -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 
mtTableMeters OBJECT-TYPE
	SYNTAX	SEQUENCE OF MtEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"A unique value for each meter."
	::= { meters 2 }

mtEntry OBJECT-TYPE
	SYNTAX	MtEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"An entry containing information applicable to a
		particular sensor."
	INDEX { mtIndex }
	::= { mtTableMeters 1 }

MtEntry ::= SEQUENCE {
	mtIndex		PositiveInteger,
	mtName		Txt16,
	mtAddr		PositiveInteger,
	mtSecAddr	PositiveInteger,
	mtValNumber PositiveInteger,
	mtSecAddrTxt Txt8	
}

mtIndex OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The meter index."
	::= { mtEntry 1 }

mtName OBJECT-TYPE
	SYNTAX	Txt16
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"Mater name."
	::= { mtEntry 2 }

mtAddr OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Meter primary address."
	::= { mtEntry 3 }

mtSecAddr OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Meter secondary address int format."
	::= { mtEntry 4 }

mtValNumber OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Number of values."
	::= { mtEntry 5 }

mtSecAddrTxt OBJECT-TYPE
	SYNTAX	Txt8
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Secondary address text format."
	::= { mtEntry 6 }	


-- Meter Value Table  -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
mtvalTableValues OBJECT-TYPE
	SYNTAX	SEQUENCE OF MtvalEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"A unique value for each meter."
	::= { meters 3 }

mtvalEntry OBJECT-TYPE
	SYNTAX	MtvalEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"An entry containing information applicable to a
		particular sensor."
	INDEX { mtvalIndex }
	::= { mtvalTableValues 1 }

MtvalEntry ::= SEQUENCE {
	mtvalIndex		 PositiveInteger,
	mtvalName		 Txt16,
	mtvalUnit		 Txt8,
	mtvalTarif		 PositiveInteger,
	mtvalExp		 PositiveInteger,
	mtvalMbusValue	 PositiveInteger,
	mtvalTxtValue	 Txt8,
	mtvalAlarmState  AlarmState,
	mtvalZeroOffset INTEGER

}

mtvalIndex OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The sensor index."
	::= { mtvalEntry 1 }

mtvalName OBJECT-TYPE
	SYNTAX	Txt16
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"Jmeno parametru."
	::= { mtvalEntry 2 }

mtvalUnit OBJECT-TYPE
	SYNTAX	Txt8
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"Jednotka parametru."
	::= { mtvalEntry 3 }

mtvalTarif OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Tarif parametru."
	::= { mtvalEntry 4 }

mtvalExp OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"Exponent parametru."
	::= { mtvalEntry 5 }

mtvalMbusValue OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Aktualni hodnota prarametru v ciselnem formatu. Hodnota bez exponentu a ZeroOffsetu"
	::= { mtvalEntry 6 }

mtvalTxtValue OBJECT-TYPE
	SYNTAX	Txt8
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Aktualni hodnota prarametru v textovem formatu. Hodnota se zapocitanym exponentm"
	::= { mtvalEntry 7 }

mtvalAlarmState OBJECT-TYPE
	SYNTAX	AlarmState
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Value Alarm State"
	::= { mtvalEntry 8 }

mtvalZeroOffset OBJECT-TYPE
	SYNTAX	INTEGER
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"Value Zero Offset."
	::= { mtvalEntry 9 }

-- Input Dry Contacts   -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
inpNumber OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"Number of Input Dry Contacts"
	::= { input 1 }

inpTable OBJECT-TYPE
	SYNTAX	SEQUENCE OF InpEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"A list of binary input entries."
	::= { input 2 }

inpEntry OBJECT-TYPE
	SYNTAX	InpEntry
	ACCESS	not-accessible
	STATUS	mandatory
	DESCRIPTION
		"An entry containing information applicable
		to a particular binary input."
	INDEX { inpIndex }
	::= { inpTable 1 }

InpEntry ::= SEQUENCE {
	inpIndex		PositiveInteger,
	inpName			Txt16,
	inpValue		OpenClose,
	inpValueName	Txt8,
	inpAlarmState	AlarmState
}

inpIndex OBJECT-TYPE
	SYNTAX	PositiveInteger
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The binary input index."
	::= { inpEntry 1 }

inpName OBJECT-TYPE
	SYNTAX	Txt16
	ACCESS	read-write
	STATUS	mandatory
	DESCRIPTION
		"The binary input name."
	::= { inpEntry 2 }

inpValue OBJECT-TYPE
	SYNTAX	OpenClose
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The binary input value."
	::= { inpEntry 3 }

inpValueName OBJECT-TYPE
	SYNTAX	Txt8
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The binary input name."
	::= { inpEntry 4 }

inpAlarmState OBJECT-TYPE
	SYNTAX	AlarmState
	ACCESS	read-only
	STATUS	mandatory
	DESCRIPTION
		"The binary input alarm state."
	::= { inpEntry 5 }

-- Trap Definitions  -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

pwrStateToAlarm	TRAP-TYPE
	ENTERPRISE	hwgpwr
	VARIABLES	{ mtvalIndex, mtvalName, mtvalUnit, mtvalTarif, mtvalExp, mtvalMbusValue, mtvalTxtValue, mtvalAlarmState }
	DESCRIPTION
		"Value changed to Alarm state."
	::= 1

pwrStateToNormal	TRAP-TYPE
	ENTERPRISE	hwgpwr
	VARIABLES	{ mtvalIndex, mtvalName, mtvalUnit, mtvalTarif, mtvalExp, mtvalMbusValue, mtvalTxtValue, mtvalAlarmState }
	DESCRIPTION
		"Value changed to Normal state."
	::= 2

inContactStateToAlarm	TRAP-TYPE
	ENTERPRISE	hwgpwr
	VARIABLES	{ sysName, infoAddressMAC, inpIndex, inpName, inpValue, inpValueName, inpAlarmState }
	DESCRIPTION
		"Input Dry Contact to Alarm state."
	::= 3

inContactStateToNormal	TRAP-TYPE
	ENTERPRISE	hwgpwr
	VARIABLES	{ sysName, infoAddressMAC, inpIndex, inpName, inpValue, inpValueName, inpAlarmState  }
	DESCRIPTION
		"Input Dry Contact to Normal state."
	::= 4





END