-- EKINOPS-Trfan.TXT:  MIB
--
--MIB Part Number:3MI00121ABAF
--MIB Version:01
--
-- Copyright (c) 2017 by Ekinops
-- All rights reserved.
-- 
-- *****************************************************************

EKINOPS-Trfan-MIB DEFINITIONS ::= BEGIN

IMPORTS
	ekinops,
	EkiState,
	EkiOnOff,
	EkiMode,
	EkiProtocol,
	EkiApiState,
	EkiMeasureType
			FROM EKINOPS-MIB
        MODULE-IDENTITY,
        OBJECT-TYPE,
        NOTIFICATION-TYPE,
	Unsigned32,
	Integer32,
	Counter32,
	IpAddress                
        		FROM SNMPv2-SMI
 	TEXTUAL-CONVENTION,
	DisplayString
                FROM SNMPv2-TC;

moduletrfan MODULE-IDENTITY
        LAST-UPDATED "201706090000Z"
        ORGANIZATION "Ekinops"
        CONTACT-INFO
         "Ekinops

          3, rue Blaise Pascal
          F-22300 Lannion / FRANCE

          Tel : +33 (0)2 96 05 00 30
          Fax : +33 (0)2 96 48 62 39

          E-mail: support@Ekinops.net"
        DESCRIPTION
          "MIB for the Ekinops Trfan hardware."

	REVISION "201001040000Z"
	DESCRIPTION
	  "Initial Version."
	REVISION "201010280000Z"
	DESCRIPTION
	  "Formula in comment"
	REVISION "201207040000Z"
	DESCRIPTION
	  "Minor cosmetic updates"
	REVISION "201309020000Z"
	DESCRIPTION
	  "Cfg StartUp-Other modification"
	REVISION "201403260000Z"
	DESCRIPTION
	  "Probcause,AlarmType - NMS completion"
	REVISION "201411250000Z"
	DESCRIPTION
	  "Labels cosmetic updates"
	REVISION "201605230000Z"
	DESCRIPTION
	  "New AlarmType  synthesisAlarm (12)"
	REVISION "201706090000Z"
	DESCRIPTION
	  "Modification of numbering of the fans"
        ::= { ekinops 45 }



--- *****************************************************
---     LEAF LEVEL 2
--- *****************************************************


trfanalarms OBJECT IDENTIFIER ::= { moduletrfan 2 }	
trfanAlmOther OBJECT IDENTIFIER ::= { trfanalarms 1 }
trfanAlmOtherNurg OBJECT IDENTIFIER ::= { trfanAlmOther 1 }
trfanAlmOtherUrg OBJECT IDENTIFIER ::= { trfanAlmOther 2 }
trfanAlmOtherCrit OBJECT IDENTIFIER ::= { trfanAlmOther 3 }



trfanmeasures OBJECT IDENTIFIER ::= { moduletrfan 3 }	
trfanMesrOther OBJECT IDENTIFIER ::= { trfanmeasures 1 }	


trfancontrolsWrite OBJECT IDENTIFIER ::= { moduletrfan 6 }
trfanCtrlOther OBJECT IDENTIFIER ::= { trfancontrolsWrite 1 }

trfanri OBJECT IDENTIFIER ::= { moduletrfan 7 }
trfanriTable OBJECT IDENTIFIER ::= { trfanri 1 }


trfanConfig OBJECT IDENTIFIER ::= { moduletrfan 9 }

trfantraps OBJECT IDENTIFIER ::= { moduletrfan 10 }

--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     TEXTUAL-CONVENTION
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************



--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     REMOTE INVENTORY
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************

trfanRinvReloadInventory OBJECT-TYPE
  SYNTAX EkiOnOff
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION
        "Reload the inventory: This OID triggers an 
         inventory reload."
  ::= { trfanri 2 }

trfanRinvHwPlatform OBJECT-TYPE
  SYNTAX DisplayString
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION
        "HW platform description: This OID contains the 
         description of the Hardware platform."
  ::= { trfanri 3 }
  
trfanRinvModulePlatform OBJECT-TYPE
  SYNTAX DisplayString
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION
        "Module platform description: This OID contains the 
         description of the Module."
  ::= { trfanri 4 }
  
trfanRinvSwPlatform OBJECT-TYPE
  SYNTAX DisplayString
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION
        "SW platform description: This OID contains the 
         description of the Software platform."
  ::= { trfanri 5 }








--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     ALARMS
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************



--- *****************************************************
---     LEAF for the synthAlm0 article
--- *****************************************************
trfanAlmsynthAlm0 OBJECT IDENTIFIER ::= { trfanAlmOtherCrit 0 }




trfanAlmDefFuse OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fuse Fail :This OID indicates
         that the fuse of the power input 
        is in fail condition.  <Help> 
         Status of the Fuse <Condtype>
         DEF_FUSE <Probcause> powerProblem 
        (36) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm0 15 }



trfanAlmAcknowledge OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Alarm Ack. :This OID indicates 
        the alarms have been acknowledged 
        by the user (locally or remotely) 
          <Help>  This status indicates 
        the alarms have been acknowledged 
        by the user (locally or remotely) 
        <Condtype> ACKNOWLEDGE <Probcause> 
        other (1) <Alarmtype> other (1) 
        <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm0 13 }



trfanAlmDefPowerB OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Power Input B Present :This OID 
        indicates that there is not input 
        power on the right power connector 
        (B).  <Help>  This alarm indicates 
        if the power input B is present 
        (right power connector) <Condtype> 
        DEF_POWER_B <Probcause> powerProblem 
        (36) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm0 12 }



trfanAlmDefPowerA OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Power Input A Present :This OID 
        indicates that there is not input 
        power on the right power connector 
        (A).  <Help>  This alarm indicates 
        if the power input B is present 
        (left power connector) <Condtype> 
        DEF_POWER_A <Probcause> powerProblem 
        (36) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm0 11 }



trfanAlmModuleGlobFailure OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Module Failure :This OID is set 
        on detection of a failure originating 
        from the PM <Condtype> MODULE_GLOB_FAILURE 
        <Probcause> equipmentMalfunction 
        (16) <Alarmtype> synthesisAlarm 
        (12)  <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm0 9 }



--- *****************************************************
---     LEAF for the synthAlm1 article
--- *****************************************************
trfanAlmsynthAlm1 OBJECT IDENTIFIER ::= { trfanAlmOtherCrit 1 }




trfanAlmFansFailure OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Chassis Fan Module Failure :This 
        OID indicates that at least one 
        of the six FAN unit of the FAN
         module is in fail condition  <Help> 
         This alarm indicates that one
         of the six fans is in a fail condition 
        <Condtype> FANS_FAILURE <Probcause> 
        heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm1 10 }



--- *****************************************************
---     LEAF for the synthAlm2 article
--- *****************************************************
trfanAlmsynthAlm2 OBJECT IDENTIFIER ::= { trfanAlmOtherNurg 2 }




trfanAlmCorrelatOff OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Not Used :This OID, when set,
         indicates that alarm correlation 
        is not being performed. <Condtype> 
        CORRELAT_OFF <Probcause> other
         (1) <Alarmtype> other (1) <Polarity> 
        (2) 
        "
	  ::= { trfanAlmsynthAlm2 4 }



trfanAlmConfTableLoad OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        PM Configuration Load :This OID 
         is at 1 during the loading of
         configuration tables in the modules 
        RAM. <Condtype> CONF_TABLE_LOAD 
        <Probcause> other (1) <Alarmtype> 
        other (1) <Polarity> (2) 
        "
	  ::= { trfanAlmsynthAlm2 3 }



trfanAlmInvUpload OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Inventory Upload :This OID is
         at 1 during the uploading of PM 
        inventory information. <Condtype> 
        INV_UPLOAD <Probcause> other (1) 
        <Alarmtype> other (1) <Polarity> 
        (2) 
        "
	  ::= { trfanAlmsynthAlm2 2 }



trfanAlmConfTableSave OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        PM Configuration Save :This OID 
        is at 1 during the saving of a
         new configuration table in the 
        module Flash memory. <Condtype> 
        CONF_TABLE_SAVE <Probcause> other 
        (1) <Alarmtype> other (1) <Polarity> 
        (2) 
        "
	  ::= { trfanAlmsynthAlm2 1 }



--- *****************************************************
---     LEAF for the filterAlm article
--- *****************************************************
trfanAlmfilterAlm OBJECT IDENTIFIER ::= { trfanAlmOtherUrg 16 }




trfanAlmFilterNotPresent OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Dust Filter Presence :This OID 
        indicates that the dust filter
         is not present  <Help>  This alarm 
        indicates that the dust filter
         is not present <Condtype> FILTER_NOT_PRESENT 
        <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfilterAlm 15 }



--- *****************************************************
---     LEAF for the fansMgnt article
--- *****************************************************
trfanAlmfansMgnt OBJECT IDENTIFIER ::= { trfanAlmOtherUrg 20 }




trfanAlmFanLowSpeed OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan High Speed :This OID indicates 
        the 6 fans of the TR-FAN are blowing 
        at high speed  <Help>  This status 
        indicates the 6 fans of the TR-FAN 
        are blowing at high speed. <Condtype> 
        FAN_LOW_SPEED <Probcause> other 
        (1) <Alarmtype> other (1) <Polarity> 
        (2) 
        "
	  ::= { trfanAlmfansMgnt 14 }



trfanAlmFansOff OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fans Fail :This OID indicates
         the 6 fans of the TR-FAN are OFF 
         <Help>  This alarm indicates the 
        6 fans of the TR-FAN are OFF <Condtype> 
        FANS_OFF <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 13 }



trfanAlmFan6Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #6 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #6. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #6 is in fail condition <Condtype> 
        FAN6_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 7 }



trfanAlmFan5Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #5 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #5. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #5 is in fail condition <Condtype> 
        FAN5_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 6 }



trfanAlmFan4Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #4 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #4. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #4 is in fail condition <Condtype> 
        FAN4_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 5 }



trfanAlmFan3Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #3 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #3. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #3 is in fail condition <Condtype> 
        FAN3_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 4 }



trfanAlmFan2Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #2 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #2. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #2 is in fail condition <Condtype> 
        FAN2_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 3 }



trfanAlmFan1Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Unit #1 Failed On Fan Module 
        :This OID indicates a failure on 
        fan #1. Removal of the fan unit 
        or no rotation sets the OID.  <Help> 
         This alarm indicates if the FAN 
        #1 is in fail condition <Condtype> 
        FAN1_FAIL <Probcause> heatingVentCoolingSystemProblem 
        (22) <Alarmtype> equipmentAlarm 
        (5) <Polarity> (2) 
        "
	  ::= { trfanAlmfansMgnt 2 }



--- *****************************************************
---     LEAF for the pwrMgnt article
--- *****************************************************
trfanAlmpwrMgnt OBJECT IDENTIFIER ::= { trfanAlmOtherUrg 24 }




trfanAlmPwr12v2Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Power 2 Fail :This OID indicates 
        a failure on the power 2 of  the 
        FAN module.  <Help>  This alarm 
        indicates if one of the two powers 
        converters of the FAN module is 
        in fail condition <Condtype> PWR_12V_2_FAIL 
        <Probcause> powerProblem (36) <Alarmtype> 
        equipmentAlarm (5) <Polarity> (2) 
        "
	  ::= { trfanAlmpwrMgnt 14 }



trfanAlmPwr12v1Fail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Fan Power 1 Fail :This OID indicates 
        a failure on the power 1 of  the 
        FAN module.  <Help>  This alarm 
        indicates if one of the two powers 
        converters of the FAN module is 
        in fail condition <Condtype> PWR_12V_1_FAIL 
        <Probcause> powerProblem (36) <Alarmtype> 
        equipmentAlarm (5) <Polarity> (2) 
        "
	  ::= { trfanAlmpwrMgnt 13 }



--- *****************************************************
---     LEAF for the modInitFailLevel2 article
--- *****************************************************
trfanAlmmodInitFailLevel2 OBJECT IDENTIFIER ::= { trfanAlmOtherUrg 70 }




trfanAlmInvReadFail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
         : <Condtype> INV_READ_FAIL <Probcause> 
        other (1) <Alarmtype> other (1) 
        <Polarity> (2) 
        "
	  ::= { trfanAlmmodInitFailLevel2 4 }



trfanAlmConfReadFail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Conf_Read_Fail : <Condtype> CONF_READ_FAIL 
        <Probcause> other (1) <Alarmtype> 
        other (1) <Polarity> (2) 
        "
	  ::= { trfanAlmmodInitFailLevel2 3 }



trfanAlmResetHwInitFail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Reset_HW_Init_Fail : <Condtype> 
        RESET_HW_INIT_FAIL <Probcause>
         other (1) <Alarmtype> other (1) 
        <Polarity> (2) 
        "
	  ::= { trfanAlmmodInitFailLevel2 2 }



trfanAlmRegReadFail OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Reg_Read_Fail : <Condtype> REG_READ_FAIL 
        <Probcause> other (1) <Alarmtype> 
        other (1) <Polarity> (2) 
        "
	  ::= { trfanAlmmodInitFailLevel2 1 }








--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     CONTROLS
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************



--- *****************************************************
---     LEAF for the synth0 article
--- *****************************************************
trfanCtrlsynth0 OBJECT IDENTIFIER ::= { trfanCtrlOther 0 }




trfanCtrlConfClear OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Clear Configuration Tables :This 
        bit clears the configuration tables 
        from configuration in the flash. 
         <Help>    This control restores 
        the default configuration of the 
        module
        "
	  ::= { trfanCtrlsynth0 13 }



trfanCtrlConfFlash OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Write Configuration Tables :This 
        bit saves the current configuration 
        of the module as configuration
         in the flash.  <Help>    This
         control saves the customer configuration 
        on the module
        "
	  ::= { trfanCtrlsynth0 9 }



trfanCtrlConfLoad OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Load Configuration Tables :When 
        set this enables loading from flash 
        configuration1 into the module.
        "
	  ::= { trfanCtrlsynth0 1 }



--- *****************************************************
---     LEAF for the synth4 article
--- *****************************************************
trfanCtrlsynth4 OBJECT IDENTIFIER ::= { trfanCtrlOther 4 }




trfanCtrlCorrelatOff OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Disable Alarm Correlation :This 
        OID disables the alarm correlation 
        in the PM.
        "
	  ::= { trfanCtrlsynth4 2 }



trfanCtrlCorrelatOn OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Enable Alarm Correlation :This 
        OID enables the alarm correlation 
        in the PM.
        "
	  ::= { trfanCtrlsynth4 1 }



--- *****************************************************
---     LEAF for the swMgnt article
--- *****************************************************
trfanCtrlswMgnt OBJECT IDENTIFIER ::= { trfanCtrlOther 5 }




trfanCtrlWarmReset OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        PM Warm Reset :This OID, when
         set, causes a warm reset of the 
        Software. This reset is not traffic 
        affecting, and the configuration 
        of the Sofwtare remains unchanged. 
         <Help>    This control initiates 
        a warm reset of the module.
        "
	  ::= { trfanCtrlswMgnt 3 }



trfanCtrlColdReset OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        PM Cold Reset :This OID, when
         set, causes a cold reset of the 
        Software. This reset is traffic 
        affecting, and the configuration 
        of Software is reloaded on start-up. 
         <Help>    This control initiates 
        a cold reset of the module.
        "
	  ::= { trfanCtrlswMgnt 2 }



--- *****************************************************
---     LEAF for the ledTest article
--- *****************************************************
trfanCtrlledTest OBJECT IDENTIFIER ::= { trfanCtrlOther 64 }




trfanCtrlLedOff OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Leds Off :This OID switches off 
        all the Leds as a test feature. 
         <Help>    This control initiates 
        a test leds turning all the LEDs 
        to OFF
        "
	  ::= { trfanCtrlledTest 3 }



trfanCtrlRedLed OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Red Leds Test :This OID switches 
        on all the red Leds as a test feature. 
         <Help>    This control initiates 
        a test leds turning all the LEDs 
        to red
        "
	  ::= { trfanCtrlledTest 2 }



trfanCtrlGreenLed OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Green Leds Test :This OID switches 
        on all the green Leds as a test 
        feature.  <Help>    This control 
        initiates a test leds turning all 
        the LEDs to green
        "
	  ::= { trfanCtrlledTest 1 }



--- *****************************************************
---     LEAF for the acknowledgeActiv article
--- *****************************************************
trfanCtrlacknowledgeActiv OBJECT IDENTIFIER ::= { trfanCtrlOther 65 }




trfanCtrlAckActiv OBJECT-TYPE
	  SYNTAX EkiOnOff
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Alarm Ack. :This OID is used to 
        acknowledge the current active
         alarms of the chassis  <Help>
          This control is used to acknowledge 
        the current active alarms of the 
        chassis
        "
	  ::= { trfanCtrlacknowledgeActiv 1 }








--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     MEASURES
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************



--- *****************************************************
---     LEAF for the voltMeas12v1 article
--- *****************************************************

trfanMesrvoltMeas12v1 OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65535)
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Internal 12V_1 :This OID gives 
        the internal voltage value of the 
        TRFAN  (Voltage = AV/500) (Unit 
        = V)  <Help>   This measure gives 
        the internal voltage value of the 
        TRFAN
        "
	  ::= { trfanMesrOther 16 }



--- *****************************************************
---     LEAF for the voltMeas12v2 article
--- *****************************************************

trfanMesrvoltMeas12v2 OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65535)
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Internal 12V_2 :This OID gives 
        the internal voltage value of the 
        TRFAN (Voltage = AV/500) (Unit
         = V)  <Help>   This measure gives 
        the internal voltage value of the 
        TRFAN
        "
	  ::= { trfanMesrOther 17 }



--- *****************************************************
---     LEAF for the tempChassis article
--- *****************************************************

trfanMesrtempChassis OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65535)
	  MAX-ACCESS read-only
	  STATUS current
	  DESCRIPTION
        "
        Chassis Temperature :This OID
         gives the temperature value of 
        the Chassis (Temperature = AV/256) 
         (Unit = C)  <Help>   This measure 
        gives the temperature value of
         the Chassis
        "
	  ::= { trfanMesrOther 64 }








--- *****************************************************
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
---     CONFIG
--- $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
--- *****************************************************



--- *****************************************************
---     LEAF for the table Group lsd
--- *****************************************************

trfanCfgLsd OBJECT IDENTIFIER ::= { trfanConfig 1 }



--- *****************************************************
---     LEAF for the table Group startUp
--- *****************************************************

trfanCfgStartUp OBJECT IDENTIFIER ::= { trfanConfig 2 }



--- *****************************************************
---     LEAF for the table 2191
--- *****************************************************

trfantableother OBJECT IDENTIFIER ::= { trfanCfgStartUp 1 }



trfanCfglowspeedThresh OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65536)
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Fans Low Speed Threshold Temp
         :This register selects the temperature 
        threshold to trigger the fans to 
        a low speed when the temperature 
        is reaching that threshold when 
        decreasing
        "
	  ::= { trfantableother 2 }



trfanCfghighspeedThresh OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65536)
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Fans High Speed Threshold Temp 
        :This register selects the temperature 
        threshold to trigger the fans to 
        a high speed when the temperature 
        is reaching that threshold when 
        increasing
        "
	  ::= { trfantableother 3 }



trfanCfgtrfanMgnt OBJECT-TYPE
	  SYNTAX Unsigned32 (0..65536)
	  MAX-ACCESS read-write
	  STATUS current
	  DESCRIPTION
        "
        Trfan Management :This register 
        selects the features to manage
         the Trfan
        "
	  ::= { trfantableother 10 }



--- *****************************************************
---     LEAF for the table Group labels
--- *****************************************************

trfanCfgLabels OBJECT IDENTIFIER ::= { trfanConfig 3 }




trfanCfgWriteConfiguration  OBJECT-TYPE
	SYNTAX EkiOnOff
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION
	"Write configuration to module:This OID 
	 writes the complete configuration to the module"
	::= { trfanConfig 257 }






--- *****************************************************
---     TRAP OBJECTS
--- *****************************************************

trfantrapBoardNumber OBJECT-TYPE
	SYNTAX INTEGER(1..64)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
	"Last module which generates a trap"
	::= { trfantraps 2 }







--- *****************************************************
---     FAN TRAPS
--- *****************************************************

trfanPowerTrapUrgentGoesOn NOTIFICATION-TYPE
	OBJECTS {trfanAlmDefPowerA, trfanAlmDefPowerB, trfanAlmPwr12v1Fail, trfanAlmPwr12v2Fail}
	STATUS current
	--&FILTNAME    "Power A Fail ON"
	--&ACTIONS     { log, major }
	--&MATCH       { trfanAlmDefPowerA "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power A Fail in Slot $3 ($A)"

	--&FILTNAME    "Power B Fail ON"
	--&ACTIONS     { log, major }
	--&MATCH       { trfanAlmDefPowerB "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power B Fail in Slot $3 ($A)"

	--&FILTNAME    "Power 12V1 Fail ON"
	--&ACTIONS     { log, major }
	--&MATCH       { trfanAlmPwr12v1Fail "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power 12V1 Fail in Slot $3 ($A)"

	--&FILTNAME    "Power 12V2 Fail ON"
	--&ACTIONS     { log, major }
	--&MATCH       { trfanAlmPwr12v2Fail "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power 12V2 Fail in Slot $3 ($A)"
	DESCRIPTION "Urgent power default is activated"
	::= { trfantraps 32 }

trfanPowerTrapUrgentGoesOff NOTIFICATION-TYPE
	OBJECTS {trfanAlmDefPowerA, trfanAlmDefPowerB, trfanAlmPwr12v1Fail, trfanAlmPwr12v2Fail}
	STATUS current
	--&FILTNAME    "Power A Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "Power A ON"}
	--&MATCH       { trfanAlmDefPowerA "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power A ON in Slot $3 ($A)"

	--&FILTNAME    "Power B Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "Power B ON"}
	--&MATCH       { trfanAlmDefPowerB "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power B ON in Slot $3 ($A)"

	--&FILTNAME    "Power 12V1 Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "Power 12V1 ON"}
	--&MATCH       { trfanAlmPwr12v1Fail "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power 12V1 ON in Slot $3 ($A)"

	--&FILTNAME    "Power 12V2 Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "Power 12V2 ON"}
	--&MATCH       { trfanAlmPwr12v2Fail "on", trfantrapBoardNumber "$3"}
	--&MESG        "Power 12V2 ON in Slot $3 ($A)"
	DESCRIPTION "Urgent power default disappeared"
	::= { trfantraps 33 }

trfanPowerTrapCritGoesOn NOTIFICATION-TYPE
	OBJECTS {trfanAlmDefFuse}
	STATUS current
	--&FILTNAME    "TRFAN Fuse Fail ON"
	--&ACTIONS     { log, critical }
	--&MATCH       { trfanAlmDefFuse "on", trfantrapBoardNumber "$3"}
	--&MESG        "Fuse Fail on TRFAN in Slot $3 ($A)"
	DESCRIPTION "Critical power default is activated"
	::= { trfantraps 34 }

trfanPowerTrapCritGoesOff NOTIFICATION-TYPE
	OBJECTS {trfanAlmDefFuse}
	STATUS current
	--&FILTNAME    "TRFAN Fuse Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "TRFAN Fuse Fail ON"}
	--&MATCH       { trfanAlmDefFuse "on", trfantrapBoardNumber "$3"}
	--&MESG        "Fuse on TRFAN present in Slot $3 ($A)"
	DESCRIPTION "Critical power default disappeared"
	::= { trfantraps 35 }






--- *****************************************************
---     Fan TRAPS
--- *****************************************************

trfanFanTrapCritGoesOn NOTIFICATION-TYPE
	OBJECTS {trfanAlmFansFailure}
	STATUS current
	--&FILTNAME    "FANs Fail ON"
	--&ACTIONS     { log, critical }
	--&MATCH       { trfanAlmFansFailure "on", trfantrapBoardNumber "$3"}
	--&MESG        "FAN Fail in Slot $3 ($A)"
	DESCRIPTION "Critical fan default is activated"
	::= { trfantraps 44 }

trfanFanTrapCritGoesOff NOTIFICATION-TYPE
	OBJECTS {trfanAlmFansFailure}
	STATUS current
	--&FILTNAME    "FANs Fail OFF"
	--&ACTIONS     { log, normal}
	--&CLEARS      { "FANs Fail ON"}
	--&MATCH       { trfanAlmFansFailure "on", trfantrapBoardNumber "$3"}
	--&MESG        "FANs OK in Slot $3 ($A)"
	DESCRIPTION "Critical fan default disappeared"
	::= { trfantraps 45 }






END