--DGPUPS-MIB { iso(1) org(3) dod(6) internet(1) private(4)
-- enterprises(1) dgp(17420) }
-- Title: DGP TOP LEVEL MIB
-- Date: January 07, 1994    Version 1.00
--
-- Date: January 17, 1994    Version 1.01
--
-- Date: July 14, 1994    Version 1.02
--
-- Date: May 16, 2003    Version 2.00

DGPUPS-MIB DEFINITIONS ::= BEGIN

IMPORTS
	TRAP-TYPE
		FROM RFC-1215
	DisplayString
		FROM RFC1213-MIB
	OBJECT-TYPE
		FROM RFC-1212
	enterprises,
	IpAddress
		FROM RFC1155-SMI;


dgp OBJECT IDENTIFIER 
   ::= { enterprises 17420 }

products OBJECT IDENTIFIER 
   ::= { dgp 1 }

ppcmgmt OBJECT IDENTIFIER 
   ::= { dgp 2 }

hardware OBJECT IDENTIFIER 
   ::= { products 1 }

mconfig OBJECT IDENTIFIER 
   ::= { ppcmgmt 1 }
  
protocol OBJECT-TYPE
   SYNTAX INTEGER {
      ups01(0),
      ups02(1),
      rpm(2),
      cps(3),
      ats(4)
   }
   ACCESS read-write
   STATUS mandatory
   DESCRIPTION
      "select protocol"
   ::= { hardware 1 }

ups OBJECT IDENTIFIER 
   ::= { hardware 2 }

upsIdentp OBJECT IDENTIFIER 
   ::= { ups 1 }

upsBatteryp OBJECT IDENTIFIER 
   ::= { ups 2 }

upsInputp OBJECT IDENTIFIER 
   ::= { ups 3 }

upsOutputp OBJECT IDENTIFIER 
   ::= { ups 4 }

upsConfigp OBJECT IDENTIFIER 
   ::= { ups 5 }

upsControlp OBJECT IDENTIFIER 
   ::= { ups 6 }

upsTestp OBJECT IDENTIFIER 
   ::= { ups 7 }

upsThreePhase OBJECT IDENTIFIER 
   ::= { ups 8 }

upsEnvironment OBJECT IDENTIFIER 
   ::= { ups 9 }

upsBaseIdent OBJECT IDENTIFIER 
   ::= { upsIdentp 1 }

upsSmartIdent OBJECT IDENTIFIER 
   ::= { upsIdentp 2 }

upsBaseBattery OBJECT IDENTIFIER 
   ::= { upsBatteryp 1 }

upsSmartBattery OBJECT IDENTIFIER 
   ::= { upsBatteryp 2 }

upsBaseInput OBJECT IDENTIFIER 
   ::= { upsInputp 1 }

upsSmartInput OBJECT IDENTIFIER 
   ::= { upsInputp 2 }

upsBaseOutput OBJECT IDENTIFIER 
   ::= { upsOutputp 1 }

upsSmartOutput OBJECT IDENTIFIER 
   ::= { upsOutputp 2 }

upsBaseConfig OBJECT IDENTIFIER 
   ::= { upsConfigp 1 }

upsSmartConfig OBJECT IDENTIFIER 
   ::= { upsConfigp 2 }

upsBaseControl OBJECT IDENTIFIER 
   ::= { upsControlp 1 }

upsSmartControl OBJECT IDENTIFIER 
   ::= { upsControlp 2 }

upsBaseTest OBJECT IDENTIFIER 
   ::= { upsTestp 1 }

upsSmartTest OBJECT IDENTIFIER 
   ::= { upsTestp 2 }

-- object types
-- the ppcmgmt group
-- the mconfig group

mconfigTrapsReceiversNum OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The number of managers to send traps to."
   ::= { mconfig 1 }


mconfigTrapsReceiversTable OBJECT-TYPE
	SYNTAX SEQUENCE OF MconfigTrapsReceiversEntry
	ACCESS not-accessible
	STATUS mandatory
	DESCRIPTION
		"A list of managers to send traps to.  The number of
		entries is given by the value of mconfigNumTrapReceivers"
   ::= { mconfig 2 }


mconfigTrapsReceiversEntry OBJECT-TYPE
	SYNTAX MconfigTrapsReceiversEntry
	ACCESS not-accessible
	STATUS mandatory
	DESCRIPTION
		"The managers to send traps to."
	INDEX {
		trapsIndex }
   ::= { mconfigTrapsReceiversTable 1 }


MconfigTrapsReceiversEntry ::= SEQUENCE {
	trapsIndex              INTEGER,
	trapsReceiverAddr       IpAddress,
	receiverCommunityString DisplayString,
	severityLevel           INTEGER,
	receiverAccept          INTEGER }


trapsIndex OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The index to a trap receiver entry."
   ::= { mconfigTrapsReceiversEntry 1 }


trapsReceiverAddr OBJECT-TYPE
	SYNTAX IpAddress
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The IP address of the manager to send a trap to."
   ::= { mconfigTrapsReceiversEntry 2 }


receiverCommunityString OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The community name to use in the trap when
		sent to the manager."
   ::= { mconfigTrapsReceiversEntry 3 }


severityLevel OBJECT-TYPE
	SYNTAX INTEGER {
			information(1),
			warning(2),
			severe(3) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The severity threshold of traps to send to the manager.
		traps are labeled in severity as informational(1), warning(2),
		severe(3).  Only traps of equal or greater severity than
		this value are sent to the manager."
   ::= { mconfigTrapsReceiversEntry 4 }


receiverAccept OBJECT-TYPE
	SYNTAX INTEGER {
			yes(1),
			no(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"An entry will become active if yes, and will
		be deleted if no."
   ::= { mconfigTrapsReceiversEntry 5 }


-- the ups group
-- the upsBaseIdent group

upsBaseIdentModel OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The UPS model name (e.g. 'Intelligent 8000E 900VA')."
   ::= { upsBaseIdent 1 }


upsBaseIdentUpsName OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"An 8 byte ID string identifying the UPS.  This object
		can be set by the administrator."
   ::= { upsBaseIdent 2 }


-- the upsSmartIdent group

upsSmartIdentFirmwareRevision OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The firmware revision of the UPS system."
   ::= { upsSmartIdent 1 }


upsSmartIdentDateOfManufacture OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The date when the UPS was manufactured in mm/dd/yy format."
   ::= { upsSmartIdent 2 }


upsSmartIdentUpsSerialNumber OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"An 8-character string identifying the serial number of
		the UPS internal microprocessor.  This number is set at
		the factory.  NOTE: This number does NOT correspond to
		the serial number on the rear of the UPS."
   ::= { upsSmartIdent 3 }


upsSmartIdentAgentFirmwareRevision OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The firmware revision of the UPS SNMP Proxy agent."
   ::= { upsSmartIdent 4 }


-- the upsBaseBattery group

upsBaseBatteryStatus OBJECT-TYPE
	SYNTAX INTEGER {
			unknown(1),
			batteryNormal(2),
			batteryLow(3) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The status of the UPS batteries.  A batteryLow(3)
		value indicates the UPS will be unable to sustain the
		current load, and its services will be lost if power is
		not restored.  The amount of run time in reserve at the
		time of low battery can be configured by the
		upsSmartConfigLowBatteryRunTime."
   ::= { upsBaseBattery 1 }


upsBaseBatteryTimeOnBattery OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The elapsed time in seconds since the UPS has switched
		to battery power."
   ::= { upsBaseBattery 2 }


upsBaseBatteryLastReplaceDate OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The date when the UPS system's batteries were last replaced
		in mm/dd/yy format.   For UPS models, this value is originally
		set in the factory.  When the UPS batteries are replaced,
		this value should be reset by the administrator."
   ::= { upsBaseBattery 3 }


-- the upsSmartBattery group

upsSmartBatteryCapacity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The remaining battery capacity expressed in
		percent of full capacity."
   ::= { upsSmartBattery 1 }


upsSmartBatteryVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current battery voltage expressed in 1/10 VDC."
   ::= { upsSmartBattery 2 }


upsSmartBatteryTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current internal UPS temperature expressed in tenths of
		a Celsius degree."
   ::= { upsSmartBattery 3 }


upsSmartBatteryRunTimeRemaining OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The UPS battery run time remaining before battery
		exhaustion, in seconds."
   ::= { upsSmartBattery 4 }


upsSmartBatteryReplaceIndicator OBJECT-TYPE
	SYNTAX INTEGER {
			noBatteryNeedsReplacing(1),
			batteryNeedsReplacing(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Indicates whether the UPS batteries need replacing."
   ::= { upsSmartBattery 5 }


upsSmartBatteryFullChargeVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The fully charged battery voltage of the battery system
		used in the UPS, expressed in tenths of a volt."
   ::= { upsSmartBattery 6 }


upsSmartBatteryCurrent OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current battery current expressed in percent of
		maximum current."
   ::= { upsSmartBattery 7 }


-- the upsBaseInput group

upsBaseInputPhase OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current AC input phase."
   ::= { upsBaseInput 1 }


-- the upsSmartInput group

upsSmartInputLineVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current utility line voltage in 1/10 VAC."
   ::= { upsSmartInput 1 }


upsSmartInputMaxLineVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The maximum utility line voltage in 1/10 VAC over the
		previous 1 minute period."
   ::= { upsSmartInput 2 }


upsSmartInputMinLineVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The minimum utility line voltage in 1/10 VAC over the
		previous 1 minute period."
   ::= { upsSmartInput 3 }


upsSmartInputFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current input frequency to the UPS system in 1/10 Hz."
   ::= { upsSmartInput 4 }


upsSmartInputLineFailCause OBJECT-TYPE
	SYNTAX INTEGER {
			noTransfer(1),
			highLineVoltage(2),
			brownout(3),
			blackout(4),
			smallMomentarySag(5),
			deepMomentarySag(6),
			smallMomentarySpike(7),
			largeMomentarySpike(8) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The reason for the occurrence of the last transfer
		to UPS battery power.  The variable is set to
		noTransfer(1) if there is no transfer yet.   The variable
		is set to highLineVoltage(2) if the transfer to battery is
		caused by an over voltage greater than the high transfer
		voltage. The variable is set to brownout(3) if the duration
		of the outage is greater than five seconds and the line
		voltage is between 40 percent of the rated output voltage and
		the low transfer voltage. The variable is set to blackout(4)
		if the duration of the outage is greater than five seconds and
		the line voltage is between 40 percent of the rated output voltage
		and ground.  The variable is set to smallMomentarySag(5)
		if the duration of the outage is less than five seconds and
		the line voltage is between 40 percent of the rated output voltage
		and the low transfer voltage.  The variable is set to
		deepMomentarySag(6) if the duration of the outage is less
		than five seconds and the line voltage is between 40 percent of the
		rated output voltage and ground."
   ::= { upsSmartInput 5 }


-- the upsBaseOutput group

upsBaseOutputStatus OBJECT-TYPE
	SYNTAX INTEGER {
			unknown(1),
			onLine(2),
			onBattery(3),
			onBoost(4),
			sleeping(5),
			onBypass(6),
			rebooting(7),
			standBy(8),
			onBuck(9) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current state of the UPS.  If the UPS is unable
		to determine the state of the UPS this variable is set
		to unknown(1)."
   ::= { upsBaseOutput 1 }


upsBaseOutputPhase OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current output phase."
   ::= { upsBaseOutput 2 }


-- the upsSmartOutput group

upsSmartOutputVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The output voltage of the UPS system in 1/10 VAC."
   ::= { upsSmartOutput 1 }


upsSmartOutputFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current output frequency of the UPS system in 1/10 Hz."
   ::= { upsSmartOutput 2 }


upsSmartOutputLoad OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current UPS load expressed in percent
		of rated capacity."
   ::= { upsSmartOutput 3 }


-- the upsBaseConfig group

upsBaseConfigNumDevices OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The number of devices that are plugged into the UPS."
   ::= { upsBaseConfig 1 }


upsBaseConfigDeviceTable OBJECT-TYPE
	SYNTAX SEQUENCE OF UpsBaseConfigDeviceEntry
	ACCESS not-accessible
	STATUS mandatory
	DESCRIPTION
		"A list of devices that are plugged into the UPS.  The
		number of entries is given by the value of
		upsBaseConfigNumDevices."
   ::= { upsBaseConfig 2 }


upsBaseConfigDeviceEntry OBJECT-TYPE
	SYNTAX UpsBaseConfigDeviceEntry
	ACCESS not-accessible
	STATUS mandatory
	DESCRIPTION
		"The devices plugged in to the UPS."
	INDEX {
		indexOfDevice }
   ::= { upsBaseConfigDeviceTable 1 }


UpsBaseConfigDeviceEntry ::= SEQUENCE {
	indexOfDevice    INTEGER,
	nameOfDevice     DisplayString,
	vaRatingOfDevice INTEGER,
	deviceAccept     INTEGER }


indexOfDevice OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The index of the device that is plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 1 }


nameOfDevice OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The name/description of the device plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 2 }


vaRatingOfDevice OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The volt-amp rating of the device plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 3 }


deviceAccept OBJECT-TYPE
	SYNTAX INTEGER {
			yes(1),
			no(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"An entry is added if yes, the entry is deleted if no."
   ::= { upsBaseConfigDeviceEntry 4 }


-- the upsSmartConfig group

upsSmartConfigRatedOutputVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The nominal output voltage from the UPS in 1/10 VAC.
		Possible values are 1000, 1200, 2080, 2200, 2250, 2300
		and 2400.
		                
		NOTE: Only units that are 2200, 2250, 2300 and 2400 can
		be changed.  Allowable values are 2200, 2250, 2300 and
		2400.
		                
		For these adjustable units, if a value other than
		a supported value is provided in a set request, the
		UPS interprets it as the next lower acceptable value.
		If the provided value is lower than the lowest acceptable
		value, the lowest acceptable value is used."
   ::= { upsSmartConfig 1 }


upsSmartConfigHighTransferVolt OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The maximum line voltage in 1/10 VAC allowed before the
		UPS system transfers to battery backup.
		                
		Allowed value depend on the UPS used:
		120 Volt units allow settings of 1290, 1320, 1350, 1380.
		100 Volt units allow settings of 1080, 1100, 1120, 1140.
		230 Volt units allow settings of 2530, 2640, 2710, 2800.
		208 Volt units allow settings of 2240, 2290, 2340, 2390.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as the next lower
		acceptable value.  If the provided value is lower than
		the lowest acceptable value, the lowest acceptable
		value is used."
   ::= { upsSmartConfig 2 }


upsSmartConfigLowTransferVolt OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The minimum line voltage in 1/10 VAC allowed before the
		UPS system transfers to battery backup.
		                
		Allowable values depend on the UPS used:
		120 Volt units allow settings of  970, 1000, 1030, 1060.
		100 Volt units allow settings of 810, 830, 850, 870.
		230 Volt units allow settings of 1880, 1960, 2040, 2080.
		208 Volt units allow settings of 1680, 1720, 1770, 1820.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 3 }


upsSmartConfigAlarm OBJECT-TYPE
	SYNTAX INTEGER {
			timed(1),
			atLowBattery(2),
			never(3) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"A flag indicating how the UPS should handle audible line fail
		alarms."
   ::= { upsSmartConfig 4 }


upsSmartConfigAlarmTimer OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The time in seconds after initial line failure at which the
		UPS begins emitting audible alarms (beeping).  This timer is
		observerd only if the value of extControlAlarm is timed(2).
		Allowed values are 0 or 30 seconds.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next lower
		acceptable value.  If the provided value is lower than
		the lowest acceptable value, the lowest acceptable
		value is used."
   ::= { upsSmartConfig 5 }


upsSmartConfigMinReturnCapacity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The minimum battery capacity as a percent of full capacity
		required before the UPS will return from a low battery
		shutdown condition.  In other words, the UPS will not
		re-energize the output until the battery capacity is equal
		to this value. Allowed values are 0, 10, 25, or 90  percent.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 6 }


upsSmartConfigSensitivity OBJECT-TYPE
	SYNTAX INTEGER {
			auto(1),
			low(2),
			medium(3),
			high(4) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The sensitivity of the UPS to utility line abnormalities
		or noises."
   ::= { upsSmartConfig 7 }


upsSmartConfigLowBatteryRunTime OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The desired run time in seconds once the low battery
		condition is reached.  Allowed values are 120, 300, 420,
		or 600 seconds.  During this time the UPS will produce a
		constant warning tone which can not be disabled.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 8 }


upsSmartConfigReturnDelay OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The delay in seconds after utility line power returns
		before the UPS will turn on.  This value is also used
		when the UPS comes out of a reboot and before the UPS
		wakes up from 'sleep' mode.  Allowed values are 0, 60,
		180 and 300 seconds.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 9 }


upsSmartConfigShutoffDelay OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The delay in seconds the UPS remains on after being told
		to turn off.  Allowed values are 12, 18, 24, 30, 36, 42,
		48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
		600 seconds.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as next higher acceptable
		value.  If the provided value is higher than the highest
		acceptable value, the highest acceptable value is used."
   ::= { upsSmartConfig 10 }


upsSmartConfigUpsSleepTime OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The time in minutes for the UPS to go to 'sleep' when
		instructed.  When in sleep mode, the UPS will not provide
		output power regardless of the input line state.  Once the
		specified time has elapsed, output power will be restored.
		                
		This is a configuration setting.  The UPS will not go to
		sleep until told to do so by the manager from a management
		station.
		                
		Any input value is allowed, however the UPS only recognizes
		0 - 9999 minutes in one minute increments.
		                
		If the provided value is higher than the highest acceptable
		value, the highest acceptable value is used."
   ::= { upsSmartConfig 11 }


upsSmartConfigSetEEPROMDefaults OBJECT-TYPE
	SYNTAX INTEGER {
			noSetEEPROMDefaults(1),
			setEEPROMDefaults(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"WRITE: Resets the UPS EEPROM variables to default values.
		READ: returns 0"
   ::= { upsSmartConfig 12 }


-- the upsBaseControl group

upsBaseControlConserveBattery OBJECT-TYPE
	SYNTAX INTEGER {
			noTurnOffUps(1),
			turnUpsOffToConserveBattery(2),
			turnUpsOffToConserveBatteryDelay(3) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to turnUpsOffToConserveBattery(2)
		causes a UPS on battery to be put into 'sleep' mode immediately.
		The (10) means suspending time(10 minutes) before turn off UPS.
		UPS will turn back on when utility power is restored.
		Attempting to turn off a UPS that is not on battery will
		result in a badValue error.
		                
		Setting this value to noTurnOffUps(1) has no
		effect.
		                
		The value noTurnOffUps(1) will always be returned
		when the variable is read."
   ::= { upsBaseControl 1 }


-- the upsSmartControl group

upsSmartControlUpsOff OBJECT-TYPE
	SYNTAX INTEGER {
			noTurnUpsOff(1),
			turnUpsOff(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to turnUpsOff(2) causes
		the UPS to shut off.  When in this state, the UPS
		will not provide output power regardless of the input
		line state.  The on/off switch on the UPS
		must be toggled for the UPS to return to operation.
		                
		Setting this value to noTurnUpsOff(1) has no
		effect.
		                
		The value noTurnUpsOff(1) will always be returned
		when the variable is read."
   ::= { upsSmartControl 1 }


upsSmartControlRebootUps OBJECT-TYPE
	SYNTAX INTEGER {
			noRebootUps(1),
			rebootUps(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to rebootUps(2) causes the
		UPS to shut off and turn back on.
		                
		Setting this value to noRebootUps(1) has no effect.
		                
		The value noRebootUps(1) will always be returned
		when the variable is read."
   ::= { upsSmartControl 2 }


upsSmartControlUpsSleep OBJECT-TYPE
	SYNTAX INTEGER {
			noPutUpsToSleep(1),
			putUpsToSleep(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to putUpsToSleep(2) causes
		the UPS to go to sleep for the time specified by
		upsSmartConfigUpsSleepTime.
		                
		When in sleep mode, the UPS will not provide output
		power regardless of the input line state.  Once the
		specified time has elapsed, output power will be
		restored.
		                
		Setting this value to noPutUpsToSleep(1) has no
		effect.
		                
		The value noPutUpsToSleep(1) will always be returned
		when the variable is read."
   ::= { upsSmartControl 3 }


upsSmartControlSimulatePowerFail OBJECT-TYPE
	SYNTAX INTEGER {
			noSimulatePowerFailure(1),
			simulatePowerFailure(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to simulatePowerFailure(2) causes
		the UPS switch to battery power.
		                
		Setting this value to noSimulatePowerFailure(1) has no
		effect.
		                
		The value noSimulatePowerFailure(1) will always be returned
		when the variable is read."
   ::= { upsSmartControl 4 }


upsSmartControlFlashAndBeep OBJECT-TYPE
	SYNTAX INTEGER {
			noFlashAndBeep(1),
			flashAndBeep(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"UPS to identify itself by lighting all indicators
		and beeping.
		                
		Setting this variable to FlashAndBeep(2) causes
		the UPS lights all panel indicators and beeps.
		                
		Setting this value to noFlashAndBeep(1) has no
		effect.
		                
		The value noFlashAndBeep(1) will always be returned
		when the variable is read."
   ::= { upsSmartControl 5 }


upsSmartControlTurnOnUpsLoad OBJECT-TYPE
	SYNTAX INTEGER {
			noUpsSmartControlTurnOnUpsLoad(1),
			upsSmartControlTurnOnUpsLoad(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to upsSmartControlTurnOnUpsLoad(2)
		causes the UPS switch back to utility power if utility
		power is present.
		                
		Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
		has no effect.
		                
		The value noUpsSmartControlTurnOnUpsLoad(1) will always
		be returned when the variable is read."
   ::= { upsSmartControl 6 }


-- the upsBaseTest group
-- the upsSmartTest group

upsSmartTestDiagnosticSchedule OBJECT-TYPE
	SYNTAX INTEGER {
			unknown(1),
			biweekly(2),
			weekly(3),
			never(4) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The UPS system's automatic battery test schedule."
  ::= { upsSmartTest 1 }


upsSmartTestDiagnostics OBJECT-TYPE
	SYNTAX INTEGER {
			noTestDiagnostics(1),
			testDiagnostics(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to testDiagnostics(2) causes
		the UPS to perform a diagnostic self test.
		                
		Setting this value to noTestDiagnostics(1) has no
		effect.
		                
		The value noTestDiagnostics(1) will always be returned
		when the variable is read."
   ::= { upsSmartTest 2 }


upsSmartTestDiagnosticsResults OBJECT-TYPE
	SYNTAX INTEGER {
			ok(1),
			failed(2),
			invalidTest(3),
			testInProgress(4) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The results of the last UPS diagnostics test performed."
   ::= { upsSmartTest 3 }


upsSmartTestLastDiagnosticsDate OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The date the last UPS diagnostics test was performed in
		mm/dd/yy format."
   ::= { upsSmartTest 4 }


upsSmartTestIndicators OBJECT-TYPE
	SYNTAX INTEGER {
			noTestIndicators(1),
			testIndicators(2) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to testIndicators(2) causes
		the UPS to perform a front panel indicator (lights) test.
		                
		Setting this value to noTestIndicators(1) has no effect.
		                
		The value noTestIndicators(1) will always be returned
		when the variable is read."
   ::= { upsSmartTest 5 }


upsSmartTestRuntimeCalibration OBJECT-TYPE
	SYNTAX INTEGER {
			noPerformCalibration(1),
			performCalibration(2),
			cancelCurrentCalibration(3) }
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to performCalibration(2) causes
		the UPS to discharge to calibrate the UPS.
		The test will only start if the battery capacity is 100 percent.
		The test runs until capacity is less than 25 percent.
		                
		Setting this variable to cancelCurrentCalibration(3)
		after setting performCalibration(2) will cancel the
		current discharge.
		                
		Setting this variable to noPerformCalibration(1)
		will have no effect.
		                
		The value noPerformCalibration(1) will always be returned
		when the variable is read.
		                
		The result of the calibration will be saved in
		upsSmartTestCalibrationResult."
   ::= { upsSmartTest 6 }


upsSmartTestCalibrationResults OBJECT-TYPE
	SYNTAX INTEGER {
			ok(1),
			invalidTest(2),
			calibrationInProgress(3) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The results of the last runtime calibration.
		                
		Value ok(1) means a successful runtime calibration.
		                
		Value invalidTest(2) indicates last calibration did
		not take place since the battery capacity was below
		100 percent.
		                
		Value calibrationInProgress(3) means a calibration
		is occurring now."
   ::= { upsSmartTest 7 }


upsSmartTestCalibrationDate OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The date the last UPS runtime calibration was
		performed in mm/dd/yy format."
   ::= { upsSmartTest 8 }


-----------------------
--ups ThreePhase group-
------------------------

upsThreePhaseBatteryGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 1 }


upsThreePhaseBatteryVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Voltage"
   ::= { upsThreePhaseBatteryGrp 1 }


upsThreePhaseBatteryCapacityPercentage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Capacity Percentage"
   ::= { upsThreePhaseBatteryGrp 2 }


upsThreePhaseBatteryTimeRemain OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Time Remain (unit is Minute)"
   ::= { upsThreePhaseBatteryGrp 3 }


upsThreePhaseBatteryCurrent OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Electric Current"
   ::= { upsThreePhaseBatteryGrp 4 }


upsThreePhaseBatteryTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Temperature"
   ::= { upsThreePhaseBatteryGrp 5 }


upsThreePhaseInputGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 2 }


upsThreePhaseInputFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Input Frequency"
   ::= { upsThreePhaseInputGrp 1 }


upsThreePhaseInputVoltageR OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Input VoltageR"
   ::= { upsThreePhaseInputGrp 2 }


upsThreePhaseInputVoltageS OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Input VoltageS"
   ::= { upsThreePhaseInputGrp 3 }


upsThreePhaseInputVoltageT OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Input VoltageT"
   ::= { upsThreePhaseInputGrp 4 }


upsThreePhaseOutputGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 3 }


upsThreePhaseOutputFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output Frequency"
   ::= { upsThreePhaseOutputGrp 1 }


upsThreePhaseOutputVoltageR OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output VoltageR"
   ::= { upsThreePhaseOutputGrp 2 }


upsThreePhaseOutputVoltageS OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output VoltageS"
   ::= { upsThreePhaseOutputGrp 3 }


upsThreePhaseOutputVoltageT OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output VoltageT"
   ::= { upsThreePhaseOutputGrp 4 }


upsThreePhaseOutputLoadPercentageR OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Load PercentageR"
   ::= { upsThreePhaseOutputGrp 5 }


upsThreePhaseOutputLoadPercentageS OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Load PercentageS"
   ::= { upsThreePhaseOutputGrp 6 }


upsThreePhaseOutputLoadPercentageT OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Load PercentageT"
   ::= { upsThreePhaseOutputGrp 7 }


upsThreePhaseBypassGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 4 }


upsThreePhaseBypassSourceFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass Frequency"
   ::= { upsThreePhaseBypassGrp 1 }


upsThreePhaseBypssSourceVoltageR OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass VoltageR"
   ::= { upsThreePhaseBypassGrp 2 }


upsThreePhaseBypssSourceVoltageS OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass VoltageS"
   ::= { upsThreePhaseBypassGrp 3 }


upsThreePhaseBypssSourceVoltageT OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass VoltageT"
   ::= { upsThreePhaseBypassGrp 4 }


upsThreePhaseDCandRectifierStatusGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 5 }


upsThreePhaseDCandRectifierStatusRecRotError OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Rectifier Rotation Error"
   ::= { upsThreePhaseDCandRectifierStatusGrp 1 }


upsThreePhaseDCandRectifierStatusLowBatteryShutdown OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Low Battery Shutdown"
   ::= { upsThreePhaseDCandRectifierStatusGrp 2 }


upsThreePhaseDCandRectifierStatusLowBattery OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Low Battery"
   ::= { upsThreePhaseDCandRectifierStatusGrp 3 }


upsThreePhaseDCandRectifierStatusInAndOut OBJECT-TYPE
	SYNTAX INTEGER {
			threeInOneOut(2),
			threeInThreeOut(3) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"In And Put"
   ::= { upsThreePhaseDCandRectifierStatusGrp 4 }


upsThreePhaseDCandRectifierStatusBatteryStatus OBJECT-TYPE
	SYNTAX INTEGER {
			backup(4),
			acnormal(5) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Back Status"
   ::= { upsThreePhaseDCandRectifierStatusGrp 5 }


upsThreePhaseDCandRectifierStatusChargeStatus OBJECT-TYPE
	SYNTAX INTEGER {
			boost(6),
			float(7),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Charge Status"
   ::= { upsThreePhaseDCandRectifierStatusGrp 6 }


upsThreePhaseDCandRectifierStatusRecOperating OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Rectifier Operating"
   ::= { upsThreePhaseDCandRectifierStatusGrp 7 }


upsThreePhaseUPSStatusGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 6 }


upsThreePhaseUPSStatusBypassFreqFail OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass Status"
   ::= { upsThreePhaseUPSStatusGrp 1 }


upsThreePhaseUPSStatusManualBypassBreaker OBJECT-TYPE
	SYNTAX INTEGER {
			close(8),
			open(9) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Breaker Status"
   ::= { upsThreePhaseUPSStatusGrp 2 }


upsThreePhaseUPSStatusACStatus OBJECT-TYPE
	SYNTAX INTEGER {
			normal(10),
			abnormal(11) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"AC Status"
   ::= { upsThreePhaseUPSStatusGrp 3 }


upsThreePhaseUPSStaticSwitchMode OBJECT-TYPE
	SYNTAX INTEGER {
			invermode(12),
			bypassmode(13) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Switch Mode"
   ::= { upsThreePhaseUPSStatusGrp 4 }


upsThreePhaseUPSStatusInverterOperating OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Operating"
   ::= { upsThreePhaseUPSStatusGrp 5 }


upsThreePhaseFaultStatusGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 7 }


upsThreePhaseFaultStatusEmergencyStop OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Emergency Stop"
   ::= { upsThreePhaseFaultStatusGrp 1 }


upsThreePhaseFaultStatusHighDCShutdown OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"High DC Shutdown"
   ::= { upsThreePhaseFaultStatusGrp 2 }


upsThreePhaseFaultStatusBypassBreaker OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass Breaker"
   ::= { upsThreePhaseFaultStatusGrp 3 }


upsThreePhaseFaultStatusOverLoad OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Over Load"
   ::= { upsThreePhaseFaultStatusGrp 4 }


upsThreePhaseFaultStatusInverterOutputFail OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output Fail"
   ::= { upsThreePhaseFaultStatusGrp 5 }


upsThreePhaseFaultStatusOverTemperature OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Over Temperature"
   ::= { upsThreePhaseFaultStatusGrp 6 }


upsThreePhaseFaultStatusShortCircuit OBJECT-TYPE
	SYNTAX INTEGER {
			yes(14),
			no(16) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Short Circuit"
   ::= { upsThreePhaseFaultStatusGrp 7 }


upsThreePhaseRatingGrp OBJECT IDENTIFIER
   ::= { upsThreePhase 8 }


upsThreePhaseRatingRectifierVoltage OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Rectifier Voltage"
   ::= { upsThreePhaseRatingGrp 1 }


upsThreePhaseRatingRectifierFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Rectifier Frequency"
   ::= { upsThreePhaseRatingGrp 2 }


upsThreePhaseRatingBypassVoltage OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass Voltage"
   ::= { upsThreePhaseRatingGrp 3 }


upsThreePhaseRatingBypassFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Bypass Frequency"
   ::= { upsThreePhaseRatingGrp 4 }


upsThreePhaseRatingOutputVoltage OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output Voltage"
   ::= { upsThreePhaseRatingGrp 5 }


upsThreePhaseRatingOutputFrequency OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Output Frequency"
   ::= { upsThreePhaseRatingGrp 6 }


upsThreePhaseRatingBatteryVoltage OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Battery Voltage"
   ::= { upsThreePhaseRatingGrp 7 }


upsThreePhaseRatingPower OBJECT-TYPE
	SYNTAX DisplayString
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Power Rating"
   ::= { upsThreePhaseRatingGrp 8 }


-----------------------
-----------------------

upsEnvStatus OBJECT IDENTIFIER 	::= { upsEnvironment 1 }

upsEnvTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The ambient environment temperature."
	::= { upsEnvStatus 1 }


upsEnvHumidity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The environment humidity."
	::= { upsEnvStatus 2 }


upsEnvOverTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Alarm dupsAlarmOverTemperature on when the environment
		temperature over the value."
	::= { upsEnvSetting 1 }


upsEnvOverHumidity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Alarm dupsAlarmOverHumidity on when the environment
		humidity over the value."
	::= { upsEnvSetting 3 }


upsEnvSecurity1 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 5 }


upsEnvSecurity2 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 6 }


upsEnvSecurity3 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 7 }


upsEnvSecurity4 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 8 }


upsEnvSecurity5 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 9 }


upsEnvSecurity6 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 10 }


upsEnvSecurity7 OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Security status"
	::= { upsEnvStatus 11 }


upsEnvWater OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Water status"
	::= { upsEnvStatus 3 }


upsEnvSmoke OBJECT-TYPE
	SYNTAX INTEGER {
			normal(1),
			abnormal(2) }
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"Smoke status"
	::= { upsEnvStatus 4 }


upsEnvSetting OBJECT IDENTIFIER 	::= { upsEnvironment 2 }

upsEnvUnderTemperature OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Alarm dupsAlarmUnderTemperature on when the environment
		temperature below the value."
	::= { upsEnvSetting 2 }


upsEnvUnderHumidity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Alarm dupsAlarmUnderHumidity on when the environment
		humidity below the value."
	::= { upsEnvSetting 4 }



communicationLost TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"SEVERE: Communication to the UPS has been lost.  Steps
		to reestablish communication are in progress."
	--#TYPE "DGP UPS: Communication failure"
	--#SUMMARY "Communication to the UPS has been lost."
	--#ARGUMENTS { }
	--#SEVERITY CRITICAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE DEGRADED
 ::= 1



upsOverLoad TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"SEVERE: The UPS has sensed a load greater than 100 percent
		of its rated capacity."
	--#TYPE "DGP UPS: UPS overload"
	--#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
	--#ARGUMENTS { }
	--#SEVERITY CRITICAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE DEGRADED
 ::= 2



upsDiagnosticsFailed TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"SEVERE: The UPS failed its internal diagnostic self-test."
	--#TYPE "DGP UPS: Failed self-test"
	--#SUMMARY "The UPS has failed its internal diagnostic self-test."
	--#ARGUMENTS { }
	--#SEVERITY CRITICAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE DEGRADED
 ::= 3



upsDischarged TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"SEVERE: The UPS just started a runtime calibration
		discharge.  The UPS batteries are being discharged."
	--#TYPE "DGP UPS: Deep discharge"
	--#SUMMARY "The UPS has just started a runtime calibration discharge."
	--#ARGUMENTS { }
	--#SEVERITY CRITICAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE DEGRADED
 ::= 4



upsOnBattery TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS has switched to battery backup power."
	--#TYPE "DGP UPS: On battery"
	--#SUMMARY "The UPS has switched to battery backup power."
	--#ARGUMENTS { }
	--#SEVERITY MAJOR
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 5



boostOn TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS has enabled Boost."
	--#TYPE "DGP UPS: SmartBoost"
	--#SUMMARY "The UPS has enabled Boost."
	--#ARGUMENTS { }
	--#SEVERITY MINOR
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 6



lowBattery TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"SEVERE: The UPS batteries are low and will soon be exhausted.
		If utility power is not restored the UPS will put itself
		to 'sleep' and immediately cut power to the load."
	--#TYPE "DGP UPS: Low battery"
	--#SUMMARY "The UPS batteries are low and will soon be exhausted."
	--#ARGUMENTS { }
	--#SEVERITY CRITICAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE DEGRADED
 ::= 7



communicationEstablished TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: Communication with the UPS has been
		established."
	--#TYPE "DGP UPS: Communication established"
	--#SUMMARY "Communication with the UPS has been established."
	--#ARGUMENTS { }
	--#SEVERITY INFORMATIONAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 8



powerRestored TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: Utility power has been restored."
	--#TYPE "DGP UPS: Utility restored"
	--#SUMMARY "Normal power has been restored to the UPS."
	--#ARGUMENTS { }
	--#SEVERITY INFORMATIONAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 9



upsDiagnosticsPassed TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: The UPS passed its internal self-test."
	--#TYPE "DGP UPS: Passed self-test"
	--#SUMMARY "The UPS has passed its internal self-test."
	--#ARGUMENTS { }
	--#SEVERITY INFORMATIONAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 10



returnFromLowBattery TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: The UPS has returned from a low battery
		condition."
	--#TYPE "DGP UPS: Battery normal"
	--#SUMMARY "The UPS has returned from a low battery condition."
	--#ARGUMENTS { }
	--#SEVERITY INFORMATIONAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 11



upsTurnedOff TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS has been turned 'off' by the
		management station."
	--#TYPE "DGP UPS: Switching off"
	--#SUMMARY "The UPS is being switched off by a management station."
	--#ARGUMENTS { }
	--#SEVERITY MAJOR
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE NONOPERATIONAL
 ::= 12



upsSleeping TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS is entering 'sleep' mode.  Power
		to the load will be cut off."
	--#TYPE "DGP UPS: Going to sleep"
	--#SUMMARY "The UPS is going into sleep mode."
	--#ARGUMENTS { }
	--#SEVERITY MAJOR
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE NONOPERATIONAL
 ::= 13



upsWokeUp TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: The UPS woke up from 'sleep' mode.  Power
		to the load has been restored."
	--#TYPE "DGP UPS: Wake up"
	--#SUMMARY "The UPS has woke up from sleep mode."
	--#ARGUMENTS { }
	--#SEVERITY INFORMATIONAL
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE OPERATIONAL
 ::= 14



upsRebootStarted TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS has started its reboot sequence.  After
			the specified delay the UPS will perform a reboot."
	--#TYPE "DGP UPS: Starting reboot"
	--#SUMMARY "The UPS has started its reboot sequence."
	--#ARGUMENTS { }
	--#SEVERITY MAJOR
	--#TIMEINDEX 1
	--#HELP ""
	--#HELPTAG 0
	--#STATE NONOPERATIONAL
 ::= 15


envOverTemperature TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The environment temperature exceed the normal value."
 ::= 16


envTemperatureNormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: The environment temperature is normal."
 ::= 17


envOverHumidity TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The environment humidity exceed the normal value."
 ::= 18


envHumidityNormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: The environment humidity is normal."
 ::= 19


envSmokeAbnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Smoke is abnormal."
 ::= 20


envWaterAbnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Water is abnormal."
 ::= 21


envSecurityAbnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security is abnormal."
 ::= 22


--envSmokeNormal TRAP-TYPE
--	ENTERPRISE dgp
--	DESCRIPTION 
--		"INFORMATION: Smoke is normal."
-- ::= 23


envWaterNormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"INFORMATION: Water is normal."
 ::= 24


envGasAbnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Gas Alarm"
 ::= 26


upsTemp TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: UPS Temperature Overrun"
 ::= 27


upsLoadNormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: UPS Load Normal"
 ::= 28


upsTempNormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: UPS temperature Normal"
 ::= 29


envUnderTemperature TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The environment temperature below the normal value."
 ::= 30


envUnderHumidity TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The environment humidity below the normal value."
 ::= 31


upsBypass TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: The UPS is entering 'bypass' mode."
 ::= 32


envSecurity1 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security1 Alarm."
 ::= 33


envSecurity2 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security2 Alarm."
 ::= 34


envSecurity3 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security3 Alarm."
 ::= 35


envSecurity4 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security4 Alarm."
 ::= 36


envSecurity5 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security5 Alarm."
 ::= 37


envSecurity6 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security6 Alarm."
 ::= 38


envSecurity7 TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Security7 Alarm."
 ::= 39

upsRecroterror TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Rectifier Rotation Error"
 ::= 47


upsBypassFreFail TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Bypass Frequency Fail"
 ::= 48


upsBypassacnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Bypass AC Normal"
 ::= 49


upsBypassacabnormal TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: Bypass AC Abnormal"
 ::= 50


upsTest TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: UPS Test"
 ::= 51


upsScheduleShutdown TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"WARNING: UPS Schedule Shutdown"
 ::= 52

upsBypassReturn TRAP-TYPE
	ENTERPRISE dgp
	DESCRIPTION 
		"The UPS return from Bypass Mode"
 ::= 53

END