-- Last edit: Thu Jan 24 13:00:00 2013
-- Jeroen Verheul
-- 
-- File: apnl-modular-pdu-v2.0.mib
-- 
-- Contact
-- Vincent Veltens <v.veltens@apnederland.nl>
-- Release version V2.0

APNL-MODULAR-PDU-MIB DEFINITIONS ::= BEGIN

IMPORTS
	NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY, 
	enterprises, IpAddress, Unsigned32, Integer32
		FROM SNMPv2-SMI
	DateAndTime, DisplayString
		FROM SNMPv2-TC;

apNederland MODULE-IDENTITY
	LAST-UPDATED "201301241000Z"
	ORGANIZATION 
		"AP Nederland"
	CONTACT-INFO 
		"Vincent Veltens <v.veltens@apnederland.nl>"
	DESCRIPTION 
		"This MIB module defines the modular PDU version of AP Nederland."

	REVISION "201301241305Z"
	DESCRIPTION 
		"Initial Version"
::= { enterprises 29640 }


-- Tue Mar 20 2012.
-- 

apnlDirectory        OBJECT IDENTIFIER ::= { apNederland 1 }
apnlMib              OBJECT IDENTIFIER ::= { apNederland 2 }
apnlTmp              OBJECT IDENTIFIER ::= { apNederland 3 }
apnlModules          OBJECT IDENTIFIER ::= { apNederland 4 }

-- Blackbox CM Communication module (mib definition is in apnl-mib.mib).

cm                   OBJECT IDENTIFIER ::= { apnlModules 1 }
cmTraps              OBJECT IDENTIFIER ::= { apnlModules 2 }

-- Modular PDU Communication module

pdu                  OBJECT IDENTIFIER ::= { apnlModules 3 }
pduTraps             OBJECT IDENTIFIER ::= { apnlModules 4 }
apnlTest             OBJECT IDENTIFIER ::= { apNederland 5 }
apnlDemo             OBJECT IDENTIFIER ::= { apNederland 6 }
apnlMIBConformance   OBJECT IDENTIFIER ::= { apNederland 7 }

pduType  OBJECT-TYPE
	SYNTAX     INTEGER {
		pduModular (0),
		pduGateway1 (1),
		pduGateway2 (2)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Type of the Pdu.
		PduModular     (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode.
		PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3).
		PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3).
		"
	::= { pdu 1 }

-- Product serial number

pduProductIdentifier  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Unique serial number to identify a pdu, the  number is between 1 and 65535. "
	::= { pdu 2 }

pduSerialNumber  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..16))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"PDU onboard Serial Number."
	::= { pdu 3 }

pduStatus  OBJECT-TYPE
	SYNTAX     INTEGER {
		pduBusy (0),
		pduReady1 (1),
		pduAlarm (2),
		pduError (3)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Status of the Pdu.
		pduBusy        (0) Indicates that an admin command is in progress.
		pduReady     (1) The execution of  an admin command was successfull.
		pduAlarm       (2) This state is not in use. 
		pduError         (3) The execution of an admin command failed."
	::= { pdu 4 }

pduPower  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"kiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured pdu power in Kilo Watt's*Hour."
	::= { pdu 5 }

pduPowerL1  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"kiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured pdu power in Kilo Watt's*Hour for phase 1."
	::= { pdu 6 }

pduPowerL2  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"kiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured pdu power in Kilo Watt's*Hour for phase 2."
	::= { pdu 7 }

pduPowerL3  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"kiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured pdu power in Kilo Watt's*Hour for phase 3."
	::= { pdu 8 }

pduKvar  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"KiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total Reactive Power of the pdu. It is the power that magnetic  equipment 
		(transformer, motor and relay) needs to produce the magnetizing flux."
	REFERENCE 
		"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
	::= { pdu 9 }

pduKvarL1  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"KiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total Reactive Power of the pdu for phase 1. It is the power that magnetic  equipment 
		(transformer, motor and relay) needs to produce the magnetizing flux."
	REFERENCE 
		"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
	::= { pdu 10 }

pduKvarL2  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"KiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total Reactive Power of the pdu for phase 2. It is the power that magnetic  equipment 
		(transformer, motor and relay) needs to produce the magnetizing flux."
	REFERENCE 
		"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
	::= { pdu 11 }

pduKvarL3  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"KiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total Reactive Power of the pdu for phase 3. It is the power that magnetic  equipment 
		(transformer, motor and relay) needs to produce the magnetizing flux."
	REFERENCE 
		"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
	::= { pdu 12 }

pdulAcurrent  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured ac current for the pdu (in 1/10th Amperes) ."
	::= { pdu 13 }

pduAcurrentL1  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured ac current for phase 1 (in 1/10th Amperes)."
	::= { pdu 14 }

pduAcurrentL2  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured ac current for phase 2 (in 1/10th Amperes)."
	::= { pdu 15 }

pduAcurrentL3  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The total measured ac current for phase 3 (in 1/10th Amperes)."
	::= { pdu 16 }

pduCurIpAddress  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The current PDU IPv4 Address by which TCP/IP access is available. 
		        "
	::= { pdu 17 }

pduCurSubNetMask  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0)."
	::= { pdu 18 }

pduCurDefGwAddress  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1)."
	::= { pdu 19 }

-- Number of items in the node table.

pduNumberOfNodes  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Number of items in the node table."
	::= { pdu 20 }

-- Number of items in the sensor table.
-- 

pduNumberOfSensors  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Number of items in the sensor table."
	::= { pdu 21 }

-- apnl upper level scalars
-- 

pduSoftwareVersion  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..10))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"PDU software version number."
	::= { pdu 22 }

pduFirmwareVersion  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..10))
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"PDU firmware version number."
	::= { pdu 23 }

pduBusProtocol  OBJECT-TYPE
	SYNTAX     INTEGER {
		apbus (0),
		modbus (1)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Selected protocol used on the external bus of the pdu.
		AP-BUS     (0) Protocol used by OEC1 products or by OEC2 products in emulation mode.
		MOD-BUS (1) Protocol used by OEC2 products."
	::= { pdu 24 }

pduAdminCommand  OBJECT-TYPE
	SYNTAX     INTEGER {
		noOp (0),
		rebootPdu (1),
		rediscover (2),
		updateSofware (3),
		resetConfig (4),
		resetSNMPv3Config (5),
		resetNetworkSetting (6),
		readDataFromBusPdu (7),
		writeDataToBusPdu (8)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"PDU admin management Commands:
		        noOp                                    (0)  No operation.
		        rebootPdu                          (1)  Reboot the PDU (to execute new settings). 
		        rediscover                         (2)   Not supported.
		        updateSofware                (3)   Not supported.
		        resetConfig                        (4)   Node  and group tables will be cleared .
		        resetSNMPv3Config       (5)  Not supported.
		        resetNetworkSetting       (6)  Reset network params: ip address, defualt gatewy, subnet mask.
		        readDataFromBusPdu  (7)  Read data from a PDU connected to the external bus (address is set in pduBusAddress).
		        writeDataToBusPdu       (8)  With this command modified data is writen back to the bus PDU (address is set in pduBusAddress).
		        "
	::= { pdu 25 }

pduStartupIpAddress  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Not supported.
		        "
	::= { pdu 26 }

pduStartupSubNetMask  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Not supported."
	::= { pdu 27 }

pduStartupDefGwAddress  OBJECT-TYPE
	SYNTAX     IpAddress
	UNITS 	"IPv4 Addr"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Not supported."
	::= { pdu 28 }

pduRealTimeClock  OBJECT-TYPE
	SYNTAX     DateAndTime
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"PDU Real-Time Clock. Maybe set by the manager."
	::= { pdu 29 }

pduEnableFeatures  OBJECT-TYPE
	SYNTAX     BITS {
		globalWebEnabled (0),
		globalUsbEnabled (1),
		globalSwitchEnabled (2),
		displaySwitchEnabled (3),
		webSwitchEnabled (4)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Array of bits each one an specific feature within the pdu:
		globalWebEnabled       (0) This bit enables the PDU webpages.
		globalUsbEnabled        (1) This bit enables the USB menu.
		globalSwitchEnabled    (2) This bit enables switching in general.
		displaySwitchEnabled  (3) This bit enables switching through the presentation module. 
		webSwitchEnabled        (4) This bit enables switching throuhg the web inteface.
		
		"
	::= { pdu 30 }

pduBusAddress  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Address used to access this PDU via the external bus.
		When MOD-BUS protocol is used the address is valid between 1-247.
		When AP-BUS protocol is used the address is valid between 1-65535.
		"
	::= { pdu 31 }

pduName  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..32))
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Name of the PDU."
	::= { pdu 32 }

-- The port table. 

nodeTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF NodeEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"A table of the modules on the PDU.
		Each entry represents an module unit.
		            "
	::= { pdu 33 }

nodeEntry  OBJECT-TYPE
	SYNTAX 	NodeEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"An port entry in the port table."
	INDEX { nodeIndex }
	::= { nodeTable 1 }

NodeEntry ::= SEQUENCE {
	nodeIndex
		Unsigned32,
	nodeType
		INTEGER,
	nodeOutlet
		Unsigned32,
	nodeAlarmStatus
		BITS,
	nodePower
		Unsigned32,
	nodeAcurrent
		Unsigned32,
	nodePeakCurrent
		Unsigned32,
	nodeVoltage
		Unsigned32,
	nodeMinVoltage
		Unsigned32,
	nodeKvar
		Unsigned32,
	nodeFrequency
		Unsigned32,
	nodePowerFactor
		Unsigned32,
	nodeSwitchOperStatus
		INTEGER,
	nodeSwitchAdminStatus
		INTEGER,
	nodeCurrHiThresh
		Unsigned32,
	nodeCurrLoThresh
		Unsigned32,
	nodeVoltHiThresh
		Unsigned32,
	nodeVoltLoThresh
		Unsigned32,
	nodeAlarmSelector
		BITS,
	nodeName
		DisplayString,
	nodePhase
		INTEGER
}

nodeIndex  OBJECT-TYPE
	SYNTAX     Unsigned32 (1..30)
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"The node table Index."
	::= { nodeEntry 1 }

nodeType  OBJECT-TYPE
	SYNTAX     INTEGER {
		typeUnknown (0),
		typePresModChar (1),
		typePresModMono (2),
		typePresModGraph (3),
		typePowerMeter (4),
		typePowerMeterSwitch (5),
		typeSwitch (6)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Type of the node.
		TypeUnknown                   (0) Unknown node.
		TypePresModChar          (1) PM LCD Character Module.
		TypePresModMono        (2) PM Mono Graphics Module.
		TypePresModGraph       (3) PM Color Graphics Module.
		TypePowerMeter              (4) Power meter.
		TypePowerMeterSwitch (5) Switchable power meter.
		TypeSwitch                         (6) Switch only.
		
		
		
		"
	::= { nodeEntry 2 }

nodeOutlet  OBJECT-TYPE
	SYNTAX     Unsigned32
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The number associated with the physical outlet of the node. 
		The special value of 0 indicates that this entry is not associated with a physical port."
	::= { nodeEntry 3 }

nodeAlarmStatus  OBJECT-TYPE
	SYNTAX     BITS {
		trapCurrHi (0),
		trapCurrLo (1),
		trapVoltHi (2),
		trapVoltLo (3),
		switchOn (4),
		switchOff (5)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Array of bits each one indicates an alarm activated in the alarm selector value.
		TrapCurrHi  (0) The current is to high against the high current threshold.
		TrapCurrLo (1) The current is to low against the low current threshold.
		TrapVoltHi  (2) The voltage is to high against the high voltage threshold.
		TrapVoltLo (3) The volage is to low against the low voltage threshold.
		SwitchOn     (4) The switch is on against the switch on bitfield.
		SwitchOff     (5) The switch is off against the switch off bitfield.
		"
	::= { nodeEntry 4 }

nodePower  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"kiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured node power in Kilo Watt's*Hour."
	::= { nodeEntry 5 }

nodeAcurrent  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured ac current at the node (in 1/10th Amperes)."
	::= { nodeEntry 6 }

nodePeakCurrent  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured max current since last reset of the node  (in 1/10th Amperes)."
	::= { nodeEntry 7 }

nodeVoltage  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Volts"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured voltage on the node."
	::= { nodeEntry 8 }

nodeMinVoltage  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Volts"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured minimum voltage at the node since last reset."
	::= { nodeEntry 9 }

nodeKvar  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"KiloWattHours"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The Reactive Power. It is the power that magnetic  equipment 
		(transformer, motor and relay) needs to produce the magnetizing flux."
	REFERENCE 
		"http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf"
	::= { nodeEntry 10 }

nodeFrequency  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Hertz"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA."
	REFERENCE 
		"http://en.wikipedia.org/wiki/Hertz"
	::= { nodeEntry 11 }

nodePowerFactor  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Percent"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The effective power facton (Cosinus Phi) in percents of the node."
	REFERENCE 
		"http://en.wikipedia.org/wiki/Power_factor"
	::= { nodeEntry 12 }

nodeSwitchOperStatus  OBJECT-TYPE
	SYNTAX     INTEGER {
		unknown (0),
		off (1),
		on (2)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The actual operational Status of the node.
		Unknown (0) not known status.
		Off              (1) switch is off.
		On              (2) switch is on."
	::= { nodeEntry 13 }

nodeSwitchAdminStatus  OBJECT-TYPE
	SYNTAX     INTEGER {
		unknown (0),
		off (1),
		on (2)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The desired admin Status of the switch.
		Unknown (0) not known.
		Off              (1) switch is off.
		On              (2) switch is on."
	::= { nodeEntry 14 }

nodeCurrHiThresh  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The current high threshold (in 1/10th Amperes)."
	::= { nodeEntry 15 }

nodeCurrLoThresh  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"DeciAmpers"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The current low threshold (in 1/10th Amperes)."
	::= { nodeEntry 16 }

nodeVoltHiThresh  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Volts"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The voltage high threshold."
	::= { nodeEntry 17 }

nodeVoltLoThresh  OBJECT-TYPE
	SYNTAX     Unsigned32
	UNITS 	"Volts"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The voltage low threshold."
	::= { nodeEntry 18 }

nodeAlarmSelector  OBJECT-TYPE
	SYNTAX     BITS {
		trapCurrHi (0),
		trapCurrLo (1),
		trapVoltHi (2),
		trapVoltLo (3),
		switchOn (4),
		switchOff (5)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Array of bits each one controls one alarm.
		TrapCurrHi  (0) Enable/disable the high current alarm.
		TrapCurrLo (1) Enable/disable the low current alarm.
		TrapVoltHi  (2) Enable/disable the high voltage alarm.
		TrapVoltLo  (3) Enable/disable the low voltage alarm.
		SwitchOn     (4) Enable/disable the specific switch on alarm.
		SwitchOff     (5) Enable/disable the specific switch off alarm."
	::= { nodeEntry 19 }

nodeName  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..14))
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The node name. My be set by manager."
	::= { nodeEntry 20 }

nodePhase  OBJECT-TYPE
	SYNTAX     INTEGER {
		phaseUnknown (0),
		phaseL1 (1),
		phaseL2 (2),
		phaseL3 (3)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The measured phase of the node. 
		Maybe assigned when not configured in production.
		PhaseUnknown (0).
		PhaseL1           (1).
		PhaseL2           (2).
		PhaseL3           (3).
		"
	::= { nodeEntry 21 }

-- 
-- The Sensors Table
-- 

sensorTable  OBJECT-TYPE
	SYNTAX SEQUENCE OF SensorEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"A table of the Sensors on the PDU.
		                Each entry represents an an Sensor unit.
		                "
	::= { pdu 34 }

sensorEntry  OBJECT-TYPE
	SYNTAX 	SensorEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"An Sensor Entry in the Sensor table"
	INDEX { sensorIndex }
	::= { sensorTable 1 }

SensorEntry ::= SEQUENCE {
	sensorIndex
		Unsigned32,
	sensorType
		INTEGER,
	sensorAlarmStatus
		BITS,
	sensorValue
		Integer32,
	sensorSwitchOperStatus
		INTEGER,
	sensorSwitchAdminStatus
		INTEGER,
	sensorHiThresh
		Integer32,
	sensorLoThresh
		Integer32,
	sensorAlarmSelector
		BITS,
	sensorName
		DisplayString
}

sensorIndex  OBJECT-TYPE
	SYNTAX     Unsigned32 (1..4)
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION 
		"The Sensor table Index."
	::= { sensorEntry 1 }

sensorType  OBJECT-TYPE
	SYNTAX     INTEGER {
		other (0),
		temperature (1),
		humidity (2),
		smoke (3),
		co1 (4),
		vibration (5),
		doorStatus (6)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Sensor Typ:
		Measured values are used according to sensor type.
		Other (0) unknown sensor type.
		Temperature (1) .
		Humidity         (2).
		Smoke            (3).
		CO1                  (4).
		Vibration         (5).
		Doorstatus     (6)."
	::= { sensorEntry 2 }

sensorAlarmStatus  OBJECT-TYPE
	SYNTAX     BITS {
		trapHi (0),
		trapLo (1),
		switchOn (2),
		switchOff (3),
		beeperHi (4),
		beeperLo (5)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"Array of bits each one indicates an alarm activated in the alarm selector value."
	::= { sensorEntry 3 }

sensorValue  OBJECT-TYPE
	SYNTAX     Integer32
	UNITS 	"by type"
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The measured value of the sensor, units are depending on sensor type."
	::= { sensorEntry 4 }

sensorSwitchOperStatus  OBJECT-TYPE
	SYNTAX     INTEGER {
		unknown (0),
		off (1),
		on (2)
	}
	MAX-ACCESS read-only
	STATUS     current
	DESCRIPTION 
		"The actual operational Status of the switch."
	::= { sensorEntry 5 }

sensorSwitchAdminStatus  OBJECT-TYPE
	SYNTAX     INTEGER {
		unknown (0),
		off (1),
		on (2)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The desired admin Status of the switch."
	::= { sensorEntry 6 }

-- thresholds

sensorHiThresh  OBJECT-TYPE
	SYNTAX     Integer32
	UNITS 	"by type"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"High threshold."
	::= { sensorEntry 7 }

sensorLoThresh  OBJECT-TYPE
	SYNTAX     Integer32
	UNITS 	"by type"
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Low threshold."
	::= { sensorEntry 8 }

sensorAlarmSelector  OBJECT-TYPE
	SYNTAX     BITS {
		trapHi (0),
		trapLo (1),
		switchOn (2),
		switchOff (3),
		beeperHi (4),
		beeperLo (5)
	}
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"Array of bits each one controls one alarm.
		E.g trap, beeper etc."
	::= { sensorEntry 9 }

sensorName  OBJECT-TYPE
	SYNTAX     DisplayString (SIZE(1..12))
	MAX-ACCESS read-write
	STATUS     current
	DESCRIPTION 
		"The sensor name. May be set by the manager."
	::= { sensorEntry 10 }

-- 
-- PDU traps
-- 
-- Trap to inform the manager about:
-- 1. voltage
-- 2. current
-- 4. sensor (temperature, humidity)
-- 5. switch
-- 6. startup
-- 7. power 
-- Trap Type enumration to indicate the kind of alarm that sent

trapType  OBJECT-TYPE
	SYNTAX     INTEGER {
		voltageHiAlarm (0),
		voltageLoAlarm (1),
		currentHiAlarm (2),
		currentLoAlarm (3),
		tempHiAlarm (4),
		tempLoAlarm (5),
		humidityHiAlarm (6),
		humidityLoAlarm (7),
		switchOnAlarm (8),
		switchOffAlarm (9),
		powerHiAlarm (10),
		blackBoxColdTrap (11)
	}
	MAX-ACCESS accessible-for-notify
	STATUS     current
	DESCRIPTION 
		"An enumation value to indicate an Alarm trap: pduPduAlarm."
	::= { pduTraps 1 }

pduTableType  OBJECT-TYPE
	SYNTAX     INTEGER {
		pduNodeTable (0),
		pduSensorTable (1)
	}
	MAX-ACCESS accessible-for-notify
	STATUS     current
	DESCRIPTION 
		"The table type."
	::= { pduTraps 2 }

-- 
-- The Index of the table entry for which the trap is made. 
-- It has the same value of the table index (which is not-accessible 
-- 

trapTableIndex  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS accessible-for-notify
	STATUS     current
	DESCRIPTION 
		"The index of the table entry for which the trap is issued."
	::= { pduTraps 3 }

-- The thershold type which the trap is made. 
-- 

trapThreshHoldType  OBJECT-TYPE
	SYNTAX     INTEGER {
		trapThresholdOther (0),
		trapThresholdHi (1),
		trapThresholdLo (2)
	}
	MAX-ACCESS accessible-for-notify
	STATUS     current
	DESCRIPTION 
		"The threshold type for which the trap is made."
	::= { pduTraps 4 }

-- The reference threshold value
-- 

trapThreshHold  OBJECT-TYPE
	SYNTAX     Integer32
	MAX-ACCESS accessible-for-notify
	STATUS     current
	DESCRIPTION 
		"The threshold reference value."
	::= { pduTraps 5 }

-- 
-- traps definitions
-- 

pduVoltageAlarm  NOTIFICATION-TYPE
	OBJECTS { trapType, 
		trapTableIndex, 
		trapThreshHoldType, 
		trapThreshHold }
	STATUS     current
	DESCRIPTION 
		"Voltage alarm."
	::= { pduTraps 6 }

pduCurrentAlarm  NOTIFICATION-TYPE
	OBJECTS { trapType, 
		trapTableIndex, 
		trapThreshHoldType, 
		trapThreshHold }
	STATUS     current
	DESCRIPTION 
		"Current alaram."
	::= { pduTraps 7 }

pduPowerAlarm  NOTIFICATION-TYPE
	OBJECTS { trapType, 
		trapTableIndex, 
		trapThreshHoldType, 
		trapThreshHold }
	STATUS     current
	DESCRIPTION 
		"Power alarm."
	::= { pduTraps 8 }

sensorAlarm  NOTIFICATION-TYPE
	OBJECTS { trapType, 
		trapTableIndex, 
		trapThreshHoldType, 
		trapThreshHold }
	STATUS     current
	DESCRIPTION 
		"Sensor Alarm: 
		Temperature, Humidity or another type. 
		The sensorType indicates the type of alarm. 
		The sensorValue indicate the measured value."
	::= { pduTraps 9 }

pduSwitchAlarm  NOTIFICATION-TYPE
	OBJECTS { trapType, 
		trapTableIndex }
	STATUS     current
	DESCRIPTION 
		"Not supported."
	::= { pduTraps 10 }
END